8500/9500 Nitrosave Oxygen Control System

Nitrosave consists of the oxygen monitor/control unit and a proportional or other control valve which is fitted into the nitrogen supply line to the machine.

Nitrosave monitors the residual oxygen in the system under control using our latest cell technology. The oxygen measurement is then used together with a fuzzy logic control algorithm and user-defined set points for desired oxygen level, to automatically control the opening of the valve, which regulates the flow of nitrogen into the machine.

This ensures enough nitrogen to comfortably maintain the desired oxygen level is fed into the machine but eliminates the  waste seen with fixed-flow nitrogen systems.


Features & Benefits

  • Save on nitrogen usage and rework costs.
  • Improve process control and product quality.
  • Automatically detects a halt in production and reduces nitrogen flow for even greater savings.
  • Extremely fast response time even after high oxygen exursions means quicker process optimization.
  • Nitrosave Viewer PC software makes set up quick and easy.
  • USB and RS485 communications output for data logging can document the whole process.
  • Small footprint allows OEM manufacturers to install inside their machines.
  • Conforms to European Directives: Electromagnetic Compatibility Directive 2004/108/EC Low Voltage Directive 73/23/EEC

Specification

Sensor Type

Dependent on Application

Ranges

0.01ppm - 100% O2 Autoranging

Accuracy

Dependent on measurement method

Measuring Cell Type

Electrochemical or Zirconia solid state, dependent on application.

Communications

USB and RS485

Alarms

2 programmable changeover contacts, rated 240V 3A

 

1 fault alarm, changeover contact, rated 240V 3A

Analog Outputs

2 scaleable 4-20mA or 0-20mA all isolated.

 

1 for control valve

Operating Conditions

 

Sample Connections

1/8 inch O/D compression

Ambient Temperature

23° to 122°F (-5 to 50°C).

Sample Gas Flow Rate

100 -300 ml/min (internal pump)

Power

230/110 VAC selectable, 80VA

Options

 

Product Sensor

Detects halt in production, software can engage new set points.

Valve Options

Flow rates dependent on oven. Consult the factory for more information.

MFC Doping Option

Air injection systems.

 

 

 




Oxygen Analyzer

Zirconia Oxygen Analyzers ZR800, Bench Top article
Zirconia Oxygen Analyzers, เครื่องวัดออกซิเจน Wall Mount IP66 article
Zirconia Oxygen Analyzers, เครื่องวัดออกซิเจต 19" Rack mount article
Paramagnetic Oxygen Analyzers, BenchTop เครื่องวัดออกซิเจน ความบริสุทธิ์สูง article
Paramagnetic Oxygen Analyzers, Wall Mount IP66 เครื่องวัดออกซิเจน ความบริสุทธิสูง article
Paramagnetic Oxygen Analyzers, Rack Mount เครื่องวัดออกซิเจน ความบริสุทธิสูง article
Intrinsically Safe Oxygen Analyzer เครื่องวัดออกซิเจน พื้นที่อันตราย มาตรฐานความปลอดภัยสูง article
EC900 Series
EC920 Series
EC930 Series
Hersch Cell ppb oxygen analyzer เครื่องวิเคราะห์ออกซิเจน ชนิดHersch
Hersch Cell ppm oxygen analyzer เครื่องวิเคราะห์ออกซิเจน ชนิดHersch
Oxygen Deficiency Monitor เครื่องวัดปริมาณออกซิเจน
ppm Oxygen Transducer ออกซิเจน เซนเซอร์
Percent Oxygen Transducer ออกซิเจน เซนเซอร์
Explosion Proof Sensor / Detector เซนเซอร์ที่ต้องอยู่ในพื้นที่อันตราย
Remote Sensor การติดตั้งเซนเซอร์แยกออกจากชุดควบคุม